SB Tech Lab — Electrical Buildout

Print Pack

Service entrance (200A), overhead/underground options, outlet circuits pull map, and panel label.

← Back to Lab

Service Entrance — 120/240V 1Ø, 200A

Overhead Service (Mast)

  • Mast-rated meter can, weatherhead/drip loops, correct service point height & clearances.
  • Guying/support if required. Use listed mast components per utility spec.

Underground Service

  • Utility-approved handhole/pedestal; proper burial depth & warning tape.
  • Conduit size/radius per conductor fill; service conductors rated wet locations.

Outlet Circuits — Pull Map (Draft)

Counts (owner): Master 4, Bedroom 2: 3, Living: 4, Kitchen: 4. Final GFCI/AFCI per AHJ.

01 — Kitchen Small Appliance — 20A GFCI
     K1 → K2 → K3 → K4  (split across two 20A circuits if heavy use)

02 — Living Room Outlets — 15A (AFCI*)
     L1 → L2 → L3 → L4

03 — Master Bedroom Outlets — 15A (AFCI*)
     M1 → M2 → M3 → M4

04 — Bedroom 2 Outlets — 15A (AFCI*)
     B1 → B2 → B3

05 — Lighting (General) — 15A

06 — Rack / Network (Dedicated) — 20A
     N1 (top of rack) → N2 (PDU feed)

07 — Mini-Split (per nameplate) — 240V 15–20A

08—10 — Spares
* If required by local code/AHJ.

Panel Directory — Tape Inside Door

SB Tech Lab — Panel Directory (120/240V 1Ø, 200A)

01  Kitchen Small Appliance (GFCI) — K1→K2→K3→K4 — 20A
02  Living Room Outlets — L1→L2→L3→L4 — 15A (AFCI*)
03  Master Bedroom Outlets — M1→M2→M3→M4 — 15A (AFCI*)
04  Bedroom 2 Outlets — B1→B2→B3 — 15A (AFCI*)
05  Lighting (General) — 15A
06  Rack / Network (Dedicated) — 20A
07  Mini-Split (per nameplate) — 240V 15–20A
08  Spare
09  Spare
10  Spare

Grounding: (2) 5/8"×8' rods ≥6' apart, #6 CU GEC. N-G bond at service disconnect only.
Inspector/Notes: ______________________  Date: __________
* If required by AHJ.